The FL-50 flame detector is capable of detecting a flame produced by a fire within its field of view within seconds.
It is particularly useful in places where a fire may develop rapidly, such as warehouses storing petroleum products, paints, plastic materials, alcohols, etc.
The operating principle is based on the detection of infrared (IR) and ultraviolet (UV) radiation emitted by a flame.

Depending on the model, the detector can be equipped with the following sensors:

  • – 3 infrared sensors with different spectral windows

  • – 1 special sensor with a spectral window in the UV range

The use of multisensor technology and special microprocessor-controlled circuitry with software featuring specific algorithms make the detector highly efficient while also highly immune to false alarms typically caused by natural disturbances or environmental factors such as lights, welding flashes, hot objects, etc.

The detector is equipped with a special internal circuit for either periodic automatic testing or manual testing via remote command

An optional automatic thermostatic system allows the detector to be used even at very low temperatures.

The device container is made of aluminum alloy with a special surface treatment against corrosion for a duration of 15 years in normal atmosphere.

The detector is in Ex-d execution with ATEX certification and has remarkable robustness and ease of installation.

FL-50 is supplied as standard with:

  • – 2 M20 ports

  • – bracket with omnidirectional joint that allows optimal orientation of the device

  • – special surface treatment against corrosion for a duration of 15 years

Applications:
• Refineries
• Gas compression stations
• Stores of petroleum products (petrol, thinners, etc.)
• Warehouses of paints
• Warehouses of paper products
• Timber and silos warehouses
• Chemical laboratories
• Deposits of flammable gases
• Landfill of waste

Technical Specifications

Power supply voltage: 11 – 3 0 Vdc
Protection: Against reverse polarity
Current: 180 mA – max
Class: 1 (for all sensitivity levels)
Maximum detection distance: 50 m (standard flame EN54-10)
ATEX zones: 1 – 2 – 21 – 22
Field of view: 90°
IR spectral response: 0,8 – 4,8 microns
UV spectral response: 15 – 260 nm
Ambient temperature: -20 + 55°C
Relative humidity: 0 – 90% non condensing RH
Thermostated optics: Automatic System
Regolation of sensitivity: 4 levels for IR and 4 for UV
Response delay: 5 – 10 – 20 – 30 sec
Alarm memory: Programmable ON/OFF
Internal electronics: Control Microprocessor
Analog voltage output: 0 – 5 V
Analog current output: 4 – 20 mA
Serial port: RS485
Operational testing: Manual and periodic automatic
Immune to electromagnetic interference: Seconda norma EN50130-4
LED status indicator: White (normal operation, pre-alarm) – Red (alarm) – Yellow
Alarm relay: 2A/250 Vac
Fault relay: 2A/250 Vac
Enclosure: Aluminum alloy with special surface protection – 15 year lifespan
Cable outlet hole: 2 cable entries M20x1.5
Protection index: IP65
Dimensions with bracket: 130×185 mm
Weight: 3 kg

Additional information

Weight 3 kg
Dimensions 185 × 130 cm